You are in:Home/Publications/2. Experimental parametric study of cooling servers management in data center buildings

Prof. Sameh A. Nada :: Publications:

Title:
2. Experimental parametric study of cooling servers management in data center buildings
Authors: 21. S.A. Nada, K.E. Elfeky, A.M.A Attia,W.G. Alshaer
Year: 2017
Keywords: Data center, experimental physical modeling, cooling management, parametric study
Journal: Not Available
Volume: Not Available
Issue: Not Available
Pages: Not Available
Publisher: Not Available
Local/International: International
Paper Link: Not Available
Full paper Sameh A. Nada_Karem paper, HMT, Springer.pdf
Supplementary materials Not Available
Abstract:

A parametric study of air flow and cooling management of data centers servers is experimentally conducted for different design conditions. A physical scale model of data center accommodating one rack of four servers was designed and constructed for testing purposes. Front and rear rack and server’s temperatures distributions and supply/return heat indices (SHI/RHI) are used to evaluate data center thermal performance. Experiments were conducted to parametrically study the effects of perforated tiles opening ratio, servers power load variation and rack power density. The results showed that (i) perforated tile of 25% opening ratio provides the best results among the other opening ratios, (ii) optimum benefit of cold air in servers cooling is obtained at uniformly power loading of servers (iii) increasing power density decrease air re-circulation but increase air bypass and servers temperature. The present results are compared with previous experimental and CFD results and fair agreement was found.

Google ScholarAcdemia.eduResearch GateLinkedinFacebookTwitterGoogle PlusYoutubeWordpressInstagramMendeleyZoteroEvernoteORCIDScopus